REQUEST INFORMATION AND CATALOG
REQUEST INFORMATION AND CATALOG

Transformers for Clinical Use

Transformers for clinical use are perfect for providing safety in the equipment and patients of hospitals and health centers.
Description

Transformers for clinical use are manufactured to ensure maximum patient safety in any area of the hospital. Their job is to isolate the external power supply of the power supply of the different utensils and machinery used in medicine and thereby ensure maximum patient safety.

These transformers have a reinforced insulation greater than 5 kv. They have totally independent windings, they also incorporate an electrostatic screen for their earth bypass.

 

Technical characteristics:

Concept Values
Isolation Class F
Frequency 50-60Hz
Type of protection IP-00
Maximum ambient temperature 45ºC
Copper type HC-210º
Dielectric strength >5000v
Leakage current <0,5 mA
Primary tension II / III 230 / 400
Secundary tension II / III 230 / 230

 

REFERENCES:

Transformers for clinical use are classified into two different series. The TMUC series are single phase transformers and the TTUC series are three phase transformers.

1.Single Phase

MODEL POWER LOSSES Vcc % WIDTH BACKGROUND TALL FIXATION FIXATION FIXATION WEIGHT
Ref. VA W UL A m/m B m/m C m/m D m/m E m/m Ø m/m KG
TMUC-1 1.000 110 4 150 160 175 125 120 7 15
TMUC-1,6 1.600 120 3,7 180 160 200 150 120 7 22
TMUC-2,5 2.500 143 3,3 180 170 200 150 130 7 25
TMUC-3 3.000 172 3,3 195 180 213 162,5 150 8 30
TMUC-4 4.000 187 3,3 195 190 213 162,5 160 8 35
TMUC-5 5.000 213 0,5 240 160 250 200 130 8 38,5
TMUC-7,5 7.500 236 3,4 240 200 250 200 170 8 46,5

 

2.Three Phases

MODEL POWER LOSSES Vcc % WIDTH BACKGROUND TALL FIXATION FIXATION FIXATION WEIGHT
Ref. VA W UL A m/m B m/m C m/m D m/m E m/m Ø m/m KG
TTUC-2 2.000 122 5 240 100 250 120 110 8 25
TTUC-3 3.000 176 5 300 120 310 200 90 8 32
TTUC-5 5.000 233 4,6 300 140 310 200 130 8 40
TTUC-7,5 7.500 356 4,5 360 130 360 320 110 8 52,5

 

Applications:

This product is ideal to ensure safety in:

  • Hospitals
  • Sanitary centers
  • Laboratory equipment
  • Operating rooms
  • UCI
  • UVI

 

Observations:

Transformers for clinical use are manufactured according to IEC 96-2, IEC-742, EN-60742 and the indicated data can be modified as needed, without prior notice.

 

Web desarrollada por 
Volcanic Internet
info
magnifiercross